General Protocol Definitions
CoolMaster PRM
5
www.xdimax.com
© 2009 XDIMAX LTD
Rev 3.0
2 General Protocol Definitions
2.1 Message format
Communication between PC or Home Automation Controller and CoolMaster via RS232 interface is
based on text messages. Communication example is shown below
>stat 101
command
PC to CoolMaster
101 ON 27C 00,00C Auto Dry OK
response
CoolMaster to PC
OK
exit code
>
prompt
Command message sent to CoolMaster must be terminated by CR (carriage return 0x0D) LF (line feed
0x0A) sequence or a single CR character. Messages from CoolMaster (except prompt character) are
terminated by CR LF. Commands are case sensitive and should not contain leading or trailing spaces.
The only separator between command name and command parameter(s) is space character.
In case of wrong command CoolMaster response can be one of the following strings:
Unrecognized command name
Command has missing or wrong parameters
If command was executed CoolMaster will return optional response and exit code. Detailed information
is provided in topics describing specific commands.
2.2 Indoor Unit Addressing
To address specific indoor unit in CoolMaster command the UID parameter is used. UID format is
three digits. First digit can be hexadecimal in range 1-9 or A-F to represent system numbers 1 to 15
correspondingly.
1
2
3
System Number
Unit Number in System
0-9, A-F
00-99
· For CoolMaster 4000M System Number must be 0, Unit Number must be 01-50
· For CoolMaster 1000D System Number must be in range 1-4
· For CoolMaster 2000S and 3000T System Number should not be 0
UID reflects the indoor unit Centralized Address. For proper operation of Cool Master all indoor units
have to be given Centralized Address (depending on specific AC system type this can be done
automatically by system or has to be done manually by integrator). You should refer to specific AC
system manuals to find out how to set and quire Centralized Addresses.
Below are examples of accepted UID's.
UID
Centralized Address
100
1-00
101
1-01
201
2-01
310
3-10
F99
15-99