56 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P - November 2009
Specifications
Measurement Accuracy and Range
Powermonitor 3000 Master Module - 1404-M4, 1404-M5, 1404-M6, 1404-M8
Parameter Accuracy in % of Full Scale at 25 °C (77 °F) 50/60 Hz Unity
Power Facator
Nominal/Range
1404-M4 1404-M5 1404-M6 1404-M8
Voltage sense
inputs: V1, V2,
V3
±0.2% ±0.05% ±0.05% ±0.05% 347V/15…399V
L-N
rms
600V/26…691V
L-L
rms
Current sense
input: I1, I2, I3, I4
±0.2% ±0.05% ±0.05% ±0.05% 5 A/50 mA…10.6 A
rms
Frequency ±0.05 Hz ±0.05 Hz ±0.05 Hz ±0.05 Hz 50 or 60 Hz/40…75 Hz
Power functions:
kW, kVA, kVAR
Demand
functions: kW,
kVA
Energy functions:
kWH, kVAH
ANSI C12.16
and
EN 61036 Class
1 Accuracy
ANSI C12.20
and
EN 60687
Class 0.5
Accuracy
(Class 0.2 is
also
available)
ANSI C12.20
and
EN 60687
Class 0.5
Accuracy
(Class 0.2 is
also
available)
ANSI
C12.20 and
EN 60687
Class 0.5
Accuracy
(Class 0.2
is also
available)
Metering update
rates
65…90 ms 55…80 ms 55…85 ms 50…100
ms
Input and Output Ratings
Attribute Value
Control power 1404-xxxxA-xxx 102…240V AC 47…63 Hz or
106…250V DC
(0.2 A max loading)
Control power 1404-xxxxB-xxx 18…50V DC (15V A max loading)
Voltage sense inputs: V1, V2, V3 Input impedance: 1 MΩ min, 399V AC max; V1, V2 and V3 to N